Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I troubleshoot the test emails failing to send on a NetBotz V3 Appliance?
Issue:
Error Message: Unable to send test email. Check appliance log.

Product Line:
NetBotz v3

Environment:
NetBotz: 355, 455, 450, and 570
NetBotz: all firmware revisions

Cause:
Misconfiguration or network issues can cause test emails to fail.

Resolution:

1) Log into the NetBotz Appliance using Advanced View.

2) Select the Configuration tab.

3) Within Appliance Settings, double-click into E-mail Server.

4) Verify the following information:
- From address (some e-mail servers require a valid from address)
- SMTP server (if using hostname, check DNS settings OR change to use IP Address)
- Port (ensure the port is not restricted on the network)
- SSL Options (if required by the e-mail server)
- Authentication (if required by the e-mail server)

5) Test E-mail Server.  If it fails, continue to step 6.

6) Under Appliance Settings, double-click into Network interfaces.

7) Ensure that the Subnet Mask, Gateway, and Hostname are correct.
NOTE: Ensure that there are no spaces within the hostname field.

8) Check your e-mail server logs to see if the emails are being rejected.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings