Video: How to install/replace a Micrologic trip unit battery?

Issue:
Replacing Display LED Battery on Micrologic 3.0, 5.0 and 6.0 Trip Units

Product Line:
Circuit Breakers Micrologic Trip Unit

Resolution:



Battery holder with battery is located under the side flap in the cardboard box the trip unit is shipped in.

1. Install battery holder with battery (P/N S33593 - A, Fig. 3) in trip unit, observing the correct polarity as indicated on the battery compartment.

2. Press test/reset button (B). All four indicator lights (C) should light. If they do not light, check polarity of battery and retest. If indicator lights still do not light up when test/reset button is pressed, stop installation and contact the local sales office for factory authorized service.

This is a 3.6V/1200mAh 1/2 "AA" Lithium battery.

Schneider Electric USA

Attachment(s)
BatteryReplacement.JPG.jpg [16.92 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings