Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the maximum current consumption on the internal +24vdc power supply on the ATV630 and ATV930 Process drives?
Issue:
Current consumption of the internal +24V DC power supply for the Altivar Process Drives ATV630/930

Product Line:
Altivar ATV630 and Altivar 930

Environment:
All

Cause:
Want to know if they can  use the drives built in +24vdc power supply to power up a PLC card.

Resolution:
24V Output power supply for digital inputs and safety
function STO inputs O =  +24 Vdc
 Tolerance: minimum 20.4 Vdc, maximum 27 Vdc
Current: maximum 200 mA for both 24 Vdc terminals
 Terminal protected against overload and short-circuit
 In Sink Ext position, this supply is powered by external PLC supply

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings