Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to troubleshoot an Altivar Process Drive with an Input Phase Fault

Article available in these languages: Japanese

Issue:
Altivar Process Drive with an Input Phase Fault.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
N/A

Resolution:
Principle:
  • Loss of one phase on the input side of the drive

Probable cause:
  • Drive incorrectly supplied or a tripped fused.
  • One phase missing.
  • 3-phase drive used on a single-phase supply mains.
  • Unbalanced load.
Remedies:
  • Check the power connection and the fuses.
  • Use a 3-phase supply mains.
  • Disable the detected error by [Input phase loss] IPL = [No] nO if single phase supply mains or DC
    bus supply is used for programming only

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings