Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I disable a logic section in Control Expert (formerly Unity)?

Issue:

How do I disable a logic section in Control Expert (formerly Unity)?

Product Line:

Logic Section, Control Expert, Unity Pro

Resolution:

Step 1: Right click on Section Name in the Browser
Step 2: Select Properties
Step 3: Select the Condition Tab
Step 4: Select a variable name from the Data Editor or create a new variable. When the variable is turned on or off you'll see a green Icon or a red Icon next to the section name indicating the section is solving (green) or its
being disabled (red)


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings