Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Video: How to install an S29450 aux, overcurrent trip, or alarm switch into a PowerPacT P frame
Issue:
How do you install an auxiliary, overcurrent trip, or alarm switch (S29450) into a PowerPacT P frame circuit breaker?

Product Line:
Molded Case Circuit Breakers

Resolution:
Make sure the breaker is in the tripped position, and then remove the four screws on the cover and remove the cover. Place the switch into one of the top three horizontal slots to the right of the handle for the OF or auxiliary functionality (changes state when the breaker contacts change state), the bottom horizontal slot to the right of the handle for the SD or alarm functionality (changes state when the breaker trips), or the vertical slot directly to the right of the handle for the SDE or overcurrent trip functionality (changes state when the breaker trips on a fault). For more information, see video below or the attached instruction bulletin:

Schneider Electric USA

Attachment(s)
Auxiliaries.PDF.pdf [2.07 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings