Do you need to reform the capacitors for a ATS48 that has not been powered up for a long time?

Issue:
Need to reform the capacitors for a ATS48

Product Line:
ATS48


Resolution:
Reforming the capacitors would not be necessary on the ATS48 because there are no DC bus capacitors. The ATS48 only has SCR's.