Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Is there a breaker rated for DC application that has an adjustable time delay setting?
Issue:
Does Square D offer a DC breaker that has a time-delay adjustment setting?

Product line:
Molded case circuit breakers

Resolution:
No. In order to have an adjustable time delay setting, the breaker must have an electronic trip unit, and no electronic trip breakers are rated for DC application.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings