Can a JGD36200 draw-out breaker be installed as a Main Breaker in an NF or I-line panelboard?
Issue:
Can the draw-out version of a Powerpact breaker be installed as the Main Breaker in an NF or I-line panelboard?

Product Line:
Drawout Breaker, J or H Frame

Environment:
Distribution Equipment

Cause:
Application.

Resolution:
NO.  The draw-out breakers like a JGD36200 are designed for a switchboard structure/application, not the panelboards (I-Line & NF).