Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Parts needed to add ERMS only to a PowerPacT P or R frame breaker with a standard trip unit

Article available in these languages: Spanish

Issue:
What is needed to add ERMS only to a PowerPacT P or R frame breaker with a standard trip unit?

Product Line:
Circuit Breakers

Resolution:
ERMS with PowerPacT P or R frame breakers is typically ordered in the factory assembled gear. If there are existing breakers without ERMS, adding it in the field CAN be done, but it has to be ordered as many individual parts. Since the gear would have been made without ERMS, there will be no provisions to add it, so it will be totally up to the installer/end user to determine a suitable and code compliant place to mount it. If field installation of ERMS is absolutely required, the below picture shows the parts that are needed. Note that this does not allow for additional communication with the trip unit, so it is only ERMS. (Addition of an IFE module would be needed)
Image of all required parts

Approximate power consumption of the above components is 11 VA @ 24 VDC
.28 VA - Switch
1.2 VA - Trip Unit
.72 VA - BCM
4 VA - I/O Module

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings