Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can I power a DC motor with an Altivar drive?
Issue:
Needs to control a DC motor with an Altivar VFD

Product Line:
All VFDs

Environment:
All

Cause:
Information needed on feature set.

Resolution:
Variable Frequency Drives are designed to power 3 phase induction type AC motors only.  They can not power single phase motors, DC motors, or Servo type motors.
They can power 3 phase asynchronous 'squirrel cage' type motors.  Some models can also power permanent magnet three phase synchronous motors but this  requires very specific information on the motor to configure properly.  Mis-configuration of a VFD on a permanent magnet motor can cause permanent damage to the magnet and render the motor inoperable.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings