Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the pulse output characteristics of PM3210 ?

Issue

What are the pulse output characteristics of the PM3210 meter?

Product Line

PowerLogic™ PM3210 Series Meter.

Environment

Energy monitoring systems where pulse output is used for interfacing with external devices such as counters, data loggers, or building management systems.

Resolution

The pulse output of the PM3210 meter is used exclusively for active energy pulse output. Key characteristics include:

  • Configurable pulse frequency (pulses/kWh)
  • Configurable pulse width, with a minimum of 50 ms
  • Pulse stop duration is equal to or longer than the pulse width
  • The pulse output reflects primary energy consumption, considering transformer ratios
  • It is important to set appropriate values for pulse frequency and pulse width to avoid pulse loss due to over-counting

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings