ClearSCADA: Adding a metadata field to provide a Description to database objects
In ClearSCADA, it is possible to add a custom 'Description' field to object properties by adding a custom metadata field.  The description field could then be queried. This article describes the steps to configuring such a metadata field.

1) In ViewX, right-click on the root group and, from the menu bar, select 'Edit Metadata'





2) In the Metadata dialog select the 'Fields' tab, click the 'Add' button and then select 'Standard'







3) Set up the new field as follows and then click OK:








4) Back in the Metadata dialog select the 'Labels' tab and click the 'Add' button.



5) Configure the label as follows and then click OK:








6) Now if you create a point and look at the 'Identification' tab you will see a new field which you can populate with a text string.







7) If you perform a query from the CDBObject table and include the ptDesc field you will see the text string that you defined for the point.





The steps above may be used as a guide for configuring other custom metadata fields.


Note: You can specify the CDBPoint table instead of the CDBObject table (steps 3 and 5 above) if you want to limit the description field to points only.  If this is done then the 'Description' field will then appear on the tab labeled 'Point' in the point properties dialog.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings