Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Video: How to tighten the wire binding screws in the AL1200P24K lug
Issue:
Where do the wires go in the AL1200P24K lug?

Product Line:
Circuit Breakers

Resolution:
The AL1200P24K lug can accept up to 4 wires per lug. See instruction document 48049-135-03 . There are 4 wire binding screws in each lug. Remove the foam spacer, and insert the first wire in the bottom left hole, and do the same for the bottom right hole. Next do the upper two holes. This picture shows the progression. Also, the following video demonstrates how this is done.

Lug image


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings