Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why does my ATS48 soft starter shows 8.8.8. on the screen?

Issue:
What does it mean when my ATS48 soft starter shows 888 on the screen.

Product line:
ATS48 series soft starters.

Environment:
All models, All serial numbers.

Cause:
Information unavailable in current literature.

Resolution:
888 on the screen, which is usually flashing, indicates a problem with the main control card CPU.  Remove power completely and then remove the front cover or Control Basket, check internal connections and reseat terminals on the front, ensuring their connection is tight.  If this doesn't resolve the 888 then it is an internal component failure of the soft starter and it is recommended to replace the  Control Basket.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings