Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Which ATV340 Drives have embedded Ethernet protocol.

Article available in these languages: Turkish


There is no option to add an Ethernet option on the non E suffix ATV340 drives.  If the Ethernet port on the ATV340.....E  fails you can not replace the module its not replaceable.  The non E suffix version or Standard ATV340 does support modbus but not Modbus TCP.

Only the E version of the ATV340.....E   drive supports Both Modbus TCP and Ethernet IP.
On a side note only the none E suffix version allow the other option cards not the E suffix version.
1:) CANopen
2: )PROFIBUS DP V1
3:) DeviceNet
4:) EtherCAT
5:) ProfiNet

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings