Issue:
Can you convert a Speed D Switchboard from a Meter Main to a Main only with no metering or remote metering?

Product Line:
Switchboard, SWBD

Environment:
Speed D Switchboard

Cause:
Application

Resolution:
The SA10BL bus link kit is used to connect the bussing, where a meter would normally be placed by the local utility. We already have a buslink installed in the C phase so you only require
1 kit for 400A Speed D boards, and 2 kits for 600A and 800A Switchboards. Switchboards that require 2 kits per phase are assembled in series to complete the current path.
This option is nice when there are no utility requirements, you have a remote meter application, or just want a main only or a  main and distribution.

The following video demonstrates how the SA10BL fits within a Speed-D switchboard:

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings