Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What can cause an INF2 fault on the ATV71 drive?

Issue:
ATV71 drive with INF2 fault.

Product Line:
ATV71

Environment:
All models

Cause:
The Drive trips in INF2 fault when the software version is incompatible with the application and control motor boards.

Resolution:
Check the reference of the power board and its compatibility.  Re-flash the control board or replace it.  Reseat the power card and control card, and try to power cycle the drive.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings