On an 800A PTMG Busway Switch, there is a cinching bolt at the bottom of it to bring the switch into the Busway. After torquing and breaking off the initial torque cap from the bolt, how do you move the switch to another location with the bolt already used once? Is there a replacement breakaway, cinching bolt/nut they are describing, that can be field installed in the event of moving?
Product Line:
I Line II Busway
Environment:
Square D Busway
Resolution:
The bolt can be re-torqued and there is no need to replace it. Please take a look at Page 21, Note 11 in the attached installation instructions.
On an 800A PTMG Busway Switch, there is a cinching bolt at the bottom of it to bring the switch into the Busway. After torquing and breaking off the initial torque cap from the bolt, how do you move the switch to another location with the bolt already used once? Is there a replacement breakaway, cinching bolt/nut they are describing, that can be field installed in the event of moving?