PowerPacT P frame motor operator wiring diagram
Issue:
How do you wire the motor of a PowerPacT P frame breaker?

Product Line:
Circuit Breakers

Resolution:
The PowerPacT P frame circuit breaker can be purchased with an internal motor operator to allow electrical operation of the breaker from a remote location. The motor must be factory installed.
When the breaker is ordered with the motor, it will include
  • motor
  • opening coil
  • closing coil
The desired voltage rating of the motor must be specified when ordering the breaker, and the opening and closing coils will then automatically have that same voltage rating (voltage supplied by the customer).
The breaker cover must be removed to access the wiring terminals. Electrical connections to the motor and coils are made as shown in the picture below.
In addition, the characteristics of the motor, trip coil, and close coil are shown below.

Wiring diagram

Motor Characteristics

Coil characteristics

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings