Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to replace an IFM TRV00210/STRV00210 by an IFM LV434000?
The IFM was updated with several improvements and changes in the design. The firmware in both units is backwards compatible with existing installations.  In addition, the new module, LV434000, is future ready as it is designed to work with the Masterpact MTZ. See detailed differences in FAQ FA321260.

Mainly impact for substitution is the Modbus connector (5-pin connector on TRV00210/STRV00210 and RJ45 for new reference LV434000)

You can then use the following accessories to operate substitution:
  • VW3A8306D30: Cables: Rj45-open
  • VW3A8306TF03 or VW3A8306TF10: T connector 3 or 10 meters
  • VW3A8306RC: Modbus line Terminator

See examples for the following cases:
<3m>3m
CentralizedWith IFEUse Case B1Use Case B4
Without IFEUse Case B2Use Case B5
DistributedUse Case B3Use Case B6

Schneider Electric USA

Attachment(s)
New IFM use case B1-B2.png [79.75 KB]
New IFM use case B3.png [85.23 KB]
New IFM use case B4-B5-B6.png [89.87 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings