Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can you adjust the motor speed with an ATS48 or ATS22 soft starters?
Issue:
Wants to adjust the motor speed with an ATS48 or ATS22 soft starters.

Product Line:
Altistart 22, Altistart 48, ATS22, ATS48

Environment:
All

Cause:
Soft starters do not have IGBTs which gate voltage/ frequency to the motor, allowing for different speeds or frequencies.

Resolution:
The soft starter will only ramp up voltage at 60 hz.   There is no option for speed control using a soft starter.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings