Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What do the different colors mean on the LED indicator for the Thermal Monitoring solution installed in the Model 6 Motor Control Center
An external single LED status indicator is provided on the unit disconnect mechanism for displaying thermal status conditions.

Solid Green - OK No Alarms                                        No Color / Black - Not Operating / Loss of Power to Device
Solid Yellow - Phase Temperature Imbalance        Flashing Yellow - Line / Load Delta Thermal
Flashing Red - High Temperature                                Solid Red - Sensor Failure Signal Loss


Temperature Alarms are configurable by dip switches.

The Thermal Monitoring solution includes Modbus RS485 serial communications capability. iMCC Network solutions with this feature are available under special order configurations.

For detailed installation and setup information reference the Exertherm instruction bulletin

For pricing and lead time information contact the Technical Assistance Group at the Seneca, SC manufacturing location.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings