Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Is line contactor mandatory for Altistarts ATS22, ATS480, ATS490?

It is required for ATS22, ATS480. Not needed for ATS490 due to presence of safety function.
If the thyristors in ATS22, ATS480 are in short-circuit or bypass relay in ATS22 is stuck, Altistart will detect it but will not be able to stop the motor, despite the active stop command from whatever channel (Logic input, PLC). Not having possibility to stop the motor is not safe situation. Altistart can only provide signalization using fault relay, but there must be a device that will react on fault signal and stop the motor. Does not need to be necessarily the contactor, it can be circuit breaker with under voltage trip for example. Altistart with fault relay will interrupt the signal on under voltage trip, so breaker will cut the current to the motor.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings