Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Altivar600, Power vs Flow curve. Does it reflect hydraulic power or does it include motor efficiency?
Altivar drive measures electrical power (from voltage and current) and considers the efficiency of the motor to give you result in form of mechanical power. Moreover, the power you enter in  Altivar drive configuration , which is also shown on motor plate is the nominal mechanical power on motor shaft. Nominal electrical power is determined by rated U, rated I and cos phi.
So power vs flow curve reflects mechanical power on motor (pump) shaft. It is not hydraulic power. If you check the pump datasheet published by pump manufacturers, the declared power is the power (mechanical) consumed by the pump.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings