Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do you properly connect or wire a transformer with the voltage code T2F?
Issue:
How is a transformer with the voltage code T2F wired or connected?

Product Line:
Transformer

Environment:
T2F transformers

Resolution:
For 480v delta to 208/120V 3 phase 4 wire.
Connect 480v to H1, H2, H3, and cap off all other H wires individually.
For 208/120V  connect X1, X2, X3 to the load and X0 to the neutral. See wiring diagram below.
wire wire1




Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings