Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why does my ATS22 S6U not run when 120VAC is closed to LI1 and LI2?

Issue:
My ATS22 S6U will not run when 120VAC is at LI1 and LI2.

Product line:
ATS22 Soft Starters

Environment:
S6U versions, All serial numbers.

Cause:
Incorrect wiring.

Resolution:
On the S6U version, it is necessary to tie Neutral not only to CL2, but also to the COM terminal.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings