Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the acceptable input voltage for an S-flex system?
Issue:
What is the acceptable input voltage for an S-flex system?

Product Line:
ATV21 and ATV212 enclosed S-flex systems.

Environment:
All models, All serial numbers.

Cause:
Voltage fluctuations at customer site.

Resolution:
The input voltage tolerance is -15% / +10% of the rating of the drive.  Note that this is the acceptable range of the equipment but may not be acceptable in your application.   As input voltage drops, motor current will increase proportionally and it is possible for the motor current to increase to a point that a motor overload condition occurs while above the minimum voltage.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings