Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Altivar Process ATV600 and Speed error in Profidrive ZSW1.8 when controlling drive on Profinet
The speed error (also known as velocity error) is the difference between the target speed setpoint and actual speed. If this value exceeds the speed error tolerance while controlling speed PID, the bit will signalize out of tolerance range.
The tolerance range cannot be set by a simple parameter. The tolerance range depends on speed loop setting (proportional gain, integral time).
This speed error bit exists on profinet/profidrive only. For other communications, ETA does not have this bit.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings