Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
S-flex runs in BYPASS mode, but will not run in AFC mode.

Issue:
S-flex not running in AFC

Product Line:
S-Flex


Resolution:
Verify that the ATV212 is in Remote mode, not Local mode.
Verify the VFD has a speed reference.  It may be running at 0Hz.
Verify operation of the DOC contactor and control power to the coil.
Check for loose connections.
Look for control component failure based on the wiring diagram and expected action.

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings