Is it possible to configure one port on the HMIGTU to communicate with a PLC on one subnet, and the other port to communicate to a PLC on a different subnet?
Issue:
Can the HMIGTU communicate to devices on two different subnets?

Product Line:
HMIGTU

Resolution:
It is possible for an Magelis HMIGTU (HMIG3U or HMIG5U) to communicate to two PLC's on a different subnets.

I have attached a screen capture on how you would configure Vijeo Designer.  The Runtime will automatically route the device to the Ethernet port on the correct subnet.

Schneider Electric USA

Attachment(s)
HMIGTU_Different Subnet comm.jpg [106.36 KB]