Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the wire type and temperature rating for Tesys D contactors?
Issue:
Customer wants to use 90C rated wires. Wants to know if they can use this on the LC1D contactors.

Product line:
IEC Style Tesys D, LC1D Contactors

Environment:
IEC Contactors and Starters

Resolution:
All IEC contactors were tested and UL listed for use with 75 Degree Celsius copper wires only for the Power circuit. The product will list this information, in addition to the instruction bulletin (see attached)
They can use 90C rated wires, but must rate these per the 75C charts in the NEC guide.

Schneider Electric USA

Attachment(s)
D09_D38 IB 1378323_ 01A55-11.pdf [776.8 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings