XW+ Stops Selling to grid in the middle of the day/when batteries are charged
Issue:
XW+ Stops Selling to grid in the middle of the day.

Product Line:
Conext XW+ Inverters

Environment:
Solar System with Sell to Grid enabled

Cause:
Grid support voltage is higher than selected Float voltage.

Resolution:
Grid Support Voltage should be lower than Float voltage. If it isn't the inverter will stop selling to the grid as soon as the Charge Controllers have fully charged the batteries (Voltage goes to Float).

Note: Make sure to have your charging settings match on both Charge Controller and Inverter.