Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to configure 8SW switch output module for low battery status?
The 8SW switch output module provides eight switch closures and can be configured to open and close based on the process value value or status of a field unit.
1. Connect PC to the Base radio and 8SW switch output module via RS485 communications.
2. Open Accutech Manager and logon.
3. Select Base & Output Devices.
4. Double click on the Analog/Digital Output module and a Output device properties window will appear.
5. Select Switch1 and configure to Monitor Field unit Status then enable the Low Battery to monitor conditions.
Accutech Manager

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings