How to Set up Accutech BR21 base radio with Aout/Switch Module
Accutech BR21 with AOUT/Switch Module set up

Instructions:
1.Connect the USB to RS485 Converter to the USB computer port.
2.Connect the 2 wire RS485 connector to the A+ and B- terminal of the BR21 Base radio.
3.Set the Dip switch 3 to RS485.
4.Apply power to the BR21 Base radio.
5.Connect the 2 wire RS485 green connector to the + - A B terminal of the Aout/Switch Module.
6.Apply power to the Aout/Switch Module using the bottom terminal.
7.Open Device manager, select Ports (COM & LPT) to verify the power created on the USB to RS485 Converter .
8.Open Accutech Manager. Use User: admin and Password: password. Hit connect.
9.At the bottom right corner of the computer screen, right click on the RF Manager service.
10.Select Options.
11.Enter the selected USB to RS485 Converter serial port.
12.Right click on the RF Manager service.
13.Then Restart the server.
14.Finish

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings