Are class R fuse clips included on the PQ plug in Units?
Issue:
Do PQ busway plug in units include Class R fuse clips?

Product Line:
Busway Plug in units

Environment:
I-line, I-lineII PQ busway units

Cause:
N/A

Resolution:
No, they are ordered as separate items. The units are supplied with Class H fuse clips as standard for 600A and below. 800A and above include class L fuse clips and do not accept any other fuses.