Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do you perform a Factory reset on the ATV12 drives?
Issue:
ATV12 back to factory configuration

Product line:
Altivar 12, ATV12

Environment:
all

Cause:
n/a

Resolution:
Navigate to the ConF menu using the dial. Push the Enter button (the dial is the Enter button). Scroll down to FCS and push Enter.
The display should say nO. Change the dial to InI. Push and hold the Enter button for 2-3s. The display will change back to nO when completed.

Note: A factory reset cannot be completed when the drive is running. The drive must be stopped.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings