Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to convert an 8538SFA21 non-fusible size 4 combo starter to fusible?
Issue:
Can you add a fuse block on a non-fusible 8538SFA21 size 4 combo starter to convert to fusible?

Product Line:
NEMA Contactors and Starters

Environment:
8538 NEMA Combination Starters

Resolution:
You cannot add a fuse block on the combo starter. You have to swap out the complete switch as the fuse block is integral of the switch.

Complete disconnect switch part number is 3105536650.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings