How to verify CM3000/CM4000 series meter KYZ operation?

Issue
How to verify CM3000/CM4000 series meter KYZ operation?

Product Line
CM3000 series meter
CM4000 series meter

Environment
Modbus Tool, Register List

Cause
How to verify the CM3000/CM4000 series KYZ pulses are being sent.

Resolution

To verify if the KYZ pulses are being sent, you can read the I/O point registers.

For example, the CM4000T Standard output (S01) registers start at 4300.
- If your looking for the IO Point Label read the register Base +1, which is register 4301.
- If your looking for the Discrete Input On/Off Status read the register Base +25, which is register 4325.
- If your looking for the Count read the register Base + 26, which is register 4326.
By referring to the IO Point Label, Discrete Input ON/Off Status and the count, you can verify the KYZ pulse operation.

To find the CM3000 and CM4000 series meter registers, please refer to FA212657.
For a simple tool that can read Modbus register, please download Modbus Tester from FA180037.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings