Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
what are the electrical characteristics of voltage inputs of DM6000H meter ?
Voltage inputs

VT primary: 100 V L-L to 999 kV L-L maximum, starting voltage depends on the VT ratio
V nominal:   Up to 277 V L-N / 480 V L-L (selectable VT secondary from 100, 110, 115, 120 to 415 V L-L)
Measured voltage with full range:  35 to 600 V AC L-L
Permanent overload (withstand):  750 V L-L, continuous
Operating voltage range with accuracy:  80-480 V L-L ± 10%, Category III
Impedance:  ≥ 5 MΩ
Frequency:   50 / 60 Hz nominal ± 2 Hz
VA burden:   ≤ 0.2 VA at 240 V AC L-N at 50Hz

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings