Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to resolve the error "Integrity check - Severe Warning!" of Unity Pro 12?
Goals and Symptoms
Unity Pro v12 pop up a window with a warning message "Integrity check - Severe Warning!"

Facts and Change
Unity Pro v12.0

Causes and Fixes
Unity Pro v12.0 shows the message below after install the UnityPro_V120_HF0435420R + UnityPro_V120_HF0437627R and recommends to re-install the Unity to correct the Sim.exe and Exec.dll, but this can be solved following the procedure below.

If this issue happens after the installation of these Hot Fixes, you can resolve it unziping the zip file and replace it on the directory showed on the message. By default the directory is C:\Program Files\Schneider Electric\PLC_Simulator

Schneider Electric USA

Attachment(s)
PLCSimulator_v12.zip [1.45 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings