Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why is Unity OSLoader showing remote device as ETY410?
Title
Unity OSLoader showing remote device as ETY410

Issue
Unity OSLoader showing wrong remote device

Product Line
Unity OSLoader

Environment
Unity Pro

Resolution
When Unity OSLoader identifies a 140CRP31200 or any other device as an ETY410, that means your FTP connection was not getting established or blocked.
Please turn off your PC's anti-virus, firewall and/or wireless adapter, so that the OSLoader FTP connection is able to be established.




Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings