Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How does the points capacity allocate when routing function is implemented in BMXNOR0200
Question:
How does the points capacity allocate when routing function is implemented in BMXNOR0200?

Answer:
If customer is using routing function(forwarding function), the points counts should include both client side & sever side. So customer have to use half of capacity points(3500) at either client side or sever side.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings