Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
ATV320 how to adjust directly the speed reference via the jog dial
Issue:
How can I adjust the speed from the jog dial on the drive?

Product Line:
Altivar ATV  Process Drive

Environment:

ALL

Cause:

Programming Wiring


Resolution:
To do the same as ATV312 after pressing Mode key.

ConF > FULL > CtL >
Fr1 = A1U1
CHCF = SEP (hold 2s)
Cd1 = tEr
ESC back to RDY

You can now press Enter (Dial) 3x to adjust the speed

Schneider Electric USA

Attachment(s)
Command terminal HM 3.docx [40.84 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings