Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What would cause an Altivar drive to respond backward to a speed reference on AI1 or AI2?
Issue:
What would cause an Altivar drive to respond backward to a speed reference on AI1 or AI2?

Product Line:
Altivar Machines

Environment:
All models and serial numbers

Cause:
Drive responds inversely to speed reference

Resolution:
This is most commonly caused by the speed reference wires being reversed.
For example: If you're using 0-10V speed potentiometer on +10V,AI1,COM, then swap your wires on +10V and COM

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings