Issue:
What is the replacement for the obsolete RIM module S48890?

Product Line:
Circuit Breakers

Environment:
RIM and ZSI Interface

Resolution:
The replacement for the RIM in ZSI applications is LV848892SP.  This module also works with the Masterpact MTZ
See attached for instructions.

Note: LV848892SP will not work for AMS applications.  For AMS applications it will be necessary to convert to the ERMS arc-flash incident Energy Reduction Maintenance System.