Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
When powering multiple ATV930 drives straight to the DC bus with a common DC power supply, what parameters need to be adjusted?
Issue:
Parameters to adjust when powering multiple ATV930 drives straight to the DC bus with a common DC power supply.

Product Line:
Altivar 930

Environment:
All

Cause:
Powering ATV930's with a single common DC power supply

Resolution:
1. Set your Access Level to Expert:
- [My Preferences] ->  [Access Level] -> [Expert]

2. Set DC Bus Source Type to Supply Unit REC:
- [Complete settings] -> [Generic functions] ->[dbS] ->[dCbS] ->[Supply Unit REC]

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings