Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Advanced One Line Application errors after upgrading from PSE 7.20 to PSE 8.2
Issue
After upgrading from PSE 7.20 to PSE 8.2, the AOL application will not animate correctly. When looking into the AdvOneLineStatusLog.txt file there are many errors similar to the following:
ERROR: WriteListHandleToPLS: Unable to Write Tag zOL\*

Product Line
PowerSCADA Expert 8.2

Environment
PowerSCADA Expert Runtime

Resolution
PSE 8.2's Advanced One Line code requires that all zol variables use the UINT type. Open the variables.dbf file and ensure that all zol variables are using the UINT type

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings