Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to control the speed of the Altivar 630 Drive with Local HMI?
Issue:
ATV630 speed control with local HMI

Product Line:
Altivar ATV600 and ATV900 series drives

Environment:
All

Cause:
The drive's speed is to be controlled by the local  HMI

Resolution:
Enter the Main Menu of the Drive. Go to Complete Settings then go to Command and Reference. In this Menu, the first parameter is Ref Freq 1 Config which is set to AI1 (Factory default), change this parameter to Ref Freq-Rmt Ter

Main Menu -> Complete Settings -> Command and Reference
-> HMI CMD to Bumpless (Default is Disabled)
-> Ref Freq 1 Config -> Ref Freq-Rmt Term
-> If Start/Stop  from Terminals and Speed control from HMI, Control Mode must be changed to Separate

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings