Issue:
Torque control set up on the ATV930 process drives.
Product Line:
ATV930 drive
Resolution:
Programming: Main menu to Complete settings to Generic Functions to Torque Control
Note that the motor control type must be set to SVCV, FVC, SYn or FSY modes.
Torque/ Speed switching (TSS)
Yes= Permanent Torque control
DI1 thru DI16 =digital inputs for switching between speed control and torque control.
CD00 thru CD10 = Virtual digital inputs CMD0 thru CMD10 for IO Profile.
CD11 thru CD15= Virtual digital input CMD11 thru CMD15 regardless of configuration.
C101 thru C110= Modbus Serial in IO Profile mode
C111 thru C115= Modbus serial in any mode
See the attached document for options configuring the Torque/Speed switching.
Torque reference Channel (where is the torque ref going to come from?)
AI1 thru AI3
AI4 thru AI5 = if you have the extended IO option card.
Ref. Freq-Rmt Term (HMI)
Ref Freq Modbus
Ref Freq CANopen
Ref Freq Com module
Embedded Ethernet
DI7 Pulse input thru DI8 Pulse input
Torque Ref Assign
Choose Digital inputs ( See attached document for more options)
Torque Ref 2 channel for 2nd torque reference. (Optional)
Torque Ref sign (Optional)
Torque Ratio= factory default is 100%
See the attached document for more Programming options.
Please note that the Drive which is in toque control will still need to run at a fixed low speed or use FR1 as the speed feedback. The torque reference will need to come form the Torque ref channel setting.
***